Eagle Eye LB-125/240-150 Battery Load Bank

$7,236.00

Eagle Eye LB-125/240-150 DC battery load bank for 125/240 V systems, 150 A discharge rating.

Description

The LB-125/240-150 is rated for 125/240 V battery systems at 150 A, with the system voltage selectable. It is the base version without the wireless DAC cell-monitoring package. Eagle Eye LB series load banks are portable DC discharge testers used to measure the real capacity of stationary battery strings. The unit draws a controlled current from the battery through PTC ceramic resistors while logging voltage and discharged capacity, then stops automatically at a preset limit. Results transfer by USB to the DataView software for analysis and reports. Models with the DAC suffix add wireless cell-voltage acquisition. Users include utilities, telecom operators, data centers and UPS service teams.

Key features

  • PTC ceramic resistors for safe discharge
  • Four auto shut-down settings: time, capacity, cell cut-off voltage and total cut-off voltage
  • Parallel connection of two units for higher currents
  • Thermal cut-off and overload protection
  • AC and DC power supply modes
  • USB data transfer and DataView analysis software

Typical applications

  • Battery capacity and acceptance testing
  • Discharge testing of UPS and telecom batteries
  • Substation and utility battery maintenance
  • Data center backup power verification

Specifications

BrandEagle Eye Power Solutions
ModelLB Series
Order codeLB-125/240-150
Product typeDC Battery Load Bank
Nominal battery voltage125/240 V
Discharge current rating150 A
Wireless DAC monitoringNo
Load typeDC, PTC ceramic resistive
Auto shut-downTime, capacity, cell voltage, total voltage
Data transferUSB drive to PC
SoftwareDataView
ConstructionPortable with carrying case

Reviews

There are no reviews yet.

Be the first to review “Eagle Eye LB-125/240-150 Battery Load Bank”

Your email address will not be published. Required fields are marked *